|
The Power-Load Chart
Estimator (see separate web page link) is
a tool to help select the electrical loads the owner wishes to power. It will
also help select the appropriate generator size. It will help the owner weigh
function (electrical loads to carry) against cost (size of generator needed).
The Basic Loads and Variable Loads are entered on the chart.
• Basic
Loads will always be connected to the generator
circuit. These electrical loads will always have power and can be operated
whenever someone uses them.
• Variable
Loads are the electrical loads that are manually
controlled and therefore can be applied in a sequence that will not overload the
generator.
This Load Chart
will help indicate which available Variable Loads can be applied
confidently knowing that the Basic Loads are always available.
On the Load
Chart, enter selected Basic Loads by entering "B" for yes in the "Basic
Loads" column. Enter "V" for Variable Loads in the "Variable Loads"
column. Enter an "X" in the "Not Used" column for loads never intended to be
powered by the generator set when utility power is out. Enter different wattages
(see manufacturers nameplate for wattage [watts = volts x amps]) for any load by
simply changing the existing value in the "Typ. Wattage" column. The total of
Basic Loads plus necessary Variable Loads determines the minimum
wattage rating generator set required. When the generator is operating,
Variable Loads plus Basic Loads should not total more than the rated
wattage of the generator selected. We suggest trying different combinations of
electrical loads to get the desired combination of
Basic & Variable Loads.
Using the attached
Manual Load Chart, the wattages are simply entered in the appropriate columns
and totaled to determine the minimum wattage rated generator set required.
For best operating
practice, the average electrical load on the generator set should not exceed 80%
of the generator's maximum power rating. Average load requirements should not be
a problem since many of the basic loads come on line intermittently (e.g., sumps
pump, well pump, furnace fan and refrigerator) and, therefore, will not all
start or be running at the same time. Motor starting factors are built into this
application guide for the loads listed. Some motors need additional wattage to
start and then fall back to their rating shown on the manufacturers nameplate.
Use the "starting amps" value on the motor nameplate to calculate the motor
starting wattage required from the generator, (watts = volts x amps). The
maximum motor starting wattage for the RS 12000 generator set is 1.6 times the
nameplate rating on the generator set.
Alternately, connecting the generator to the
entire house distribution panel allows all loads to be selectively powered, but
this requires the homeowner to be more careful to limit electrical loads applied
to the generator set. (See the RST Transfer Selection Guidelines for more
information on selecting the appropriate interconnection method.) If certain
electrical loads are identified and isolated for use by the generator when using
an electrical sub-panel, the Basic & Variable Loads will not overload the
system.
|